Skip to content
English
  • There are no suggestions because the search field is empty.

Sensor near power cables – what minimum distance is required?

Rule of thumb for minimum distances depending on the current (target: B ≤ 1 mT), plus notes on ferromagnetic materials.

The influence depends on the current in the conductor and its distance from the sensor.

Copper cables are not ferromagnetic. What matters is the magnetic field generated by the current flowing through them.

Ferromagnetic materials nearby (e.g., steel parts, rebar, grounding conductors in or near steel) can also have an influence.

Minimum distance (rule of thumb for B ≤ 1 mT)

mindestabstand-B-1mT_EN

Current Minimum distance
100 A approx. 2 cm
250 A approx. 5 cm
500 A approx. 10 cm
1,000 A approx. 20 cm
2,000 A approx. 40 cm

Note:

  • Avoid distances of less than 5 cm from ferromagnetic materials, such as sheet metal, galvanized steel, magnets, or steel grounding conductors.
  • These distances are guide values. If in doubt, increase the distance or change the installation position.

If you have any questions, please contact our support team at support@suessco.com.